AquaCal Heat Pump Error Codes & Troubleshooting
What Every Code Means and When to Call a Pro
Seeing a code on your AquaCal HeatWave SuperQuiet, HeatWave or TropiCal heat pump? Pick your model or type your code below to see what it means, what to check first, and how urgent it is.
No code on the display, or the code isn’t the problem? Use our pool heater troubleshooting guide.
✓ HVAC & EPA 608 Certified | ✓ 30+ Years Experience | ✓ 90-Day Workmanship Warranty
Doing a DIY repair? We can guide you over the phone.
Need a professional repair? We’ll fix it fast.
FREE to schedule. No obligation. No credit card needed
3 Things to Try Before Calling a Technician
Power-cycle
Turn the heat pump off, then the circuit breaker. Wait 5 minutes and restore power. This also clears lockouts like HP5 and LP5.
Check water flow
Most AquaCal codes (FLO, LOW, HP, HIGH PRESSURE FAULT, AL15) are caused by low water flow, not a broken part. Confirm the pump is on and running fast enough, the filter is clean, and water isn’t being diverted away from the heat pump.
Check outside temp
Heat pumps slow down or stop in cold weather. LP, LOW PRESSURE FAULT, FS (defrost) and AL14 can show up when it’s cold. If they keep showing once it warms up, call us.
Disclaimer: This page is for informational purposes only. Heat pumps involve electricity, refrigerant, and moving parts, and internal repairs should always be done by a qualified technician. Improper service may void your warranty or cause injury.
Most Common AquaCal Error Codes
These codes cover most AquaCal service calls. Older models show short codes (like FLO), current models show words (like HIGH PRESSURE FAULT), and the TropiCal Inverter uses AL and EA codes. Don’t see yours? Find it by model below.
AquaCal FLO and LOW Codes: Low or No Water Flow
FLO (older models) and LOW (TropiCal Inverter) mean the heat pump isn’t getting enough water. On the TropiCal Inverter, AL15 means the water leaving is much warmer than the water coming in, which also points to low flow.
- Make sure the pool pump is on. If it’s a variable-speed pump, run it at a higher speed.
- Make sure the filter is clean and not in backwash.
- Make sure valves aren’t diverting water away from the heat pump.
If the code comes back with good flow, the water pressure switch may need adjusting or replacing.
Still showing a flow code? Schedule a repair or call 407-786-0000.
AquaCal HP and HIGH PRESSURE FAULT: High Refrigerant Pressure (HP, HP5, AL10, AL11)
HP and HIGH PRESSURE FAULT mean the refrigerant high pressure switch has opened. On AquaCal heat pumps the usual cause is low water flow. HP5 (or HP5 SYSTEM LOCKOUT) means it happened 5 times in one heating call and the heat pump locked out. On the TropiCal Inverter, the same codes are AL10 and AL11.
- Make sure the pool pump is on. If it’s a variable-speed pump, run it at a higher speed.
- Make sure the filter is clean and not in backwash.
- Make sure valves aren’t diverting water away from the heat pump.
If it locks out again after you cycle power, turn it off and call. Running it this way strains the compressor.
Still showing HP? Schedule a repair or call 407-786-0000.
AquaCal LP and LOW PRESSURE FAULT: Low Refrigerant Pressure (LP, LP5, AL12, AL13)
LP and LOW PRESSURE FAULT mean the refrigerant low pressure switch has opened. Common causes are a fan that isn’t running, blocked airflow, a dirty evaporator coil, heavy ice on the coil, or low refrigerant from a leak. LP5 means it locked out after 5 trips. On the TropiCal Inverter, the same codes are AL12 and AL13.
- Clear leaves and debris from around the coil.
- Check that the fan is spinning when the heat pump runs.
If LP shows up on a warm day or keeps coming back, it’s often a refrigerant leak. Only an EPA 608 certified tech can test and recharge refrigerant, and our techs are certified.
Still showing LP? Schedule a repair or call 407-786-0000.
AquaCal FS Code: Defrost Cycle
FS means the heat pump is defrosting its coil. When ice starts to form, it pauses heating for about 10 minutes and sends warm refrigerant through the coil. You may see steam coming off the unit while it melts.
If FS comes back over and over, or shows on a mild day, the defrost sensor may be failing.
Still showing FS? Schedule a repair or call 407-786-0000.
AquaCal OtA and HIGH WATER TEMP: Water Too Hot
OtA (older models) and OTA SYSTEM LOCKOUT or HIGH WATER TEMP (current models) mean the water coming in is too hot, above about 108–110°F. The usual cause is a gas or solar heater sending hot water straight into the heat pump. If that’s not it, a water temperature sensor is reading wrong.
Still showing OtA? Schedule a repair or call 407-786-0000.
AquaCal Sensor Codes (pC, pO, dPC, dPO, WATER TEMP, DEFROST, AL01–AL06)
These mean the control board isn’t getting a good reading from a sensor. pC/pO and WATER TEMP1/2 are the water sensors, dPC/dPO and DEFROST1/2 are the defrost sensors, and AL01–AL06 are the TropiCal Inverter’s sensors.
The sensor or its wiring usually needs to be tested and replaced. Until a water sensor is replaced, newer AquaCals limit the setpoint to 96°F.
Still showing a sensor code? Schedule a repair or call 407-786-0000.
AquaCal Control and Display Codes (CEr, CSE, NO CONTROLLER COMM, AL07)
These mean the control board and display aren’t talking. CSE often clears by cycling power. CEr, NO CONTROLLER COMM and AL07 usually point to a loose or damaged display cable.
Still showing one of these codes? Schedule a repair or call 407-786-0000.
AquaCal TropiCal Inverter Compressor Codes (AL18–AL25, EA01–EA19)
These are the TropiCal Inverter’s compressor, voltage, and inverter drive protections. Most of them lock the heat pump out to prevent damage. Turn it off and call; these need a certified tech.
Still showing one of these codes? Schedule a repair or call 407-786-0000.
AquaCal Heat Pump Troubleshooting
No code on the display, but your AquaCal still isn’t working right? These are the checks AquaCal recommends and our techs run first.
AquaCal Heat Pump Not Running or Won't Turn On
- Blank display? Check that both the main breaker and the disconnect switch next to the heat pump are on.
- Display on but not running? Make sure it’s set to HEAT mode and the setpoint is above the current water temperature.
- Just turned it on? AquaCal heat pumps wait up to 3–4 minutes before the compressor starts.
- Using automation or an outside controller? The heat pump may not be set to accept its signal.
- Code on the display? Look it up below.
Still not running? Schedule a repair or call 407-786-0000.
AquaCal Running But Not Heating
- Confirm HEAT mode and a setpoint above the water temperature.
- Check valves are sending water to the right place. If you’re heating a spa that spills into the pool, isolate the spa.
- Run the pool pump long enough. The heat pump only heats while water is flowing.
- Turn off waterfalls, fountains and spa blowers, and use a cover. They lose heat fast.
- Quick check: air blowing out of the fan should feel 8–16°F colder than the outside air. If it doesn’t, the heat pump isn’t moving heat into the water.
If the air isn’t colder, or the pool still won’t warm up, the refrigerant system or a part needs a tech. Schedule a repair or call 407-786-0000.
Ice or Frost on Your AquaCal
A light layer of white frost on the coil can form in cold weather before the heat pump goes into defrost (FS). Heavy ice is different. If ice keeps building up, turn the heat pump off and call. On heat/cool models with active defrost, frost can build for up to 50 minutes before it defrosts. If it doesn’t defrost by then, call.
If it’s going to stay below 32°F for more than 8 hours, the heat pump should be winterized. Schedule a repair or call 407-786-0000.
AquaCal Breaker Keeps Tripping
Don’t keep resetting it. A breaker that trips over and over can mean the wrong breaker size, a failing breaker, a wiring problem, or a compressor or fan problem. Have an electrician or certified tech check it. Schedule a repair or call 407-786-0000.
Water Coming From Your AquaCal: Leak or Condensation?
Heat pumps make a lot of condensation while they run, especially on humid days. To check, turn the heat pump off and leave the pool pump running for a few hours. If the water stops, it was condensation. If it keeps coming, test it with a pool test strip. Chlorine in the water means a leak inside the unit. Schedule a repair or call 407-786-0000.
How Do I Test the Sensor on My AquaCal?
If a sensor code shows up (pC, pO, dPC, dPO, WATER TEMP, DEFROST, or AL01–AL06 on TropiCal Inverters), the sensor or its wiring has failed. Testing one means measuring its resistance with a meter and comparing it to AquaCal’s chart at the current temperature, so it’s a job for a tech. Until a water sensor is replaced, newer AquaCals limit the setpoint to 96°F. Schedule a repair or call 407-786-0000.
Find your code below
Type your error code in the search box, or pick your model and tap your code.
We cover current AquaCal HeatWave SuperQuiet, HeatWave and TropiCal Inverter heat pumps, plus previous SuperQuiet and TropiCal models.
Different brand? See pool heater error codes for every brand.
AquaCal HeatWave SuperQuiet Error Codes

All fault messages for current AquaCal HeatWave SuperQuiet heat pumps.
Models: SQ140R and SQ200R (plus TC1000 and TC1500 chillers).
AquaCal HeatWave SuperQuiet Code Table
Code | What It Means | Likely Cause | What to do |
|---|---|---|---|
COMPRESSOR LOCKOUT | Compressor failed to start and went into protection mode | Compressor or start component problem | Turn off & call now |
HIGH PRESSURE FAULT | Refrigerant high pressure switch open | Low water flow (pump off or slow, water diverted away from the heat pump). On cool-only units: fan not running, blocked airflow or a dirty coil | Call soon |
LOW PRESSURE FAULT | Refrigerant low pressure switch open | Fan not running, blocked airflow, dirty evaporator coil or heavy ice on the coil; low refrigerant from a leak | Call soon |
HIGH WATER TEMP | Incoming water above 108°F; heat pump shut off until it drops to 100°F | A gas or solar heater sending hot water straight to the heat pump, or a failed water temperature sensor | Call soon |
HP5 SYSTEM LOCKOUT | Locked out after 5 high pressure faults in one heating or cooling call | The high pressure problem keeps happening. Clears by cycling power | Turn off & call now |
LP5 SYSTEM LOCKOUT | Locked out after 5 low pressure faults in one heating or cooling call | The low pressure problem keeps happening. Clears by cycling power | Turn off & call now |
HPC TEMP SYSTEM LOCKOUT | Control board overheating | Control board or cooling problem | Call soon |
OTA SYSTEM LOCKOUT | Water over a safe temperature (above 110°F) or the two water sensors disagree; heat pump shut off | Out-of-calibration or failed water sensor, or water heated by another source | Call soon |
DEFROST1 / DEFROST2 SENSOR OPEN | Defrost sensor open | Failed defrost sensor or wiring | Call soon |
DEFROST1 / DEFROST2 SENSOR SHORT | Defrost sensor shorted | Failed defrost sensor or wiring | Call soon |
WATER TEMP1 / WATER TEMP2 SENSOR SHORT or OPEN | Water temperature sensor shorted or open; setpoint limited to 96°F until replaced | Failed water sensor or wiring | Call soon |
NO CONTROLLER COMM | Heat pump can't talk to the display board | Loose or damaged cable between the control board and display | Call if it comes back |
ERROR AT PRIMARY UNIT | This is a secondary heat pump and the primary unit has a fault | A fault on the primary heat pump | Call if it comes back |
MULTIPLE PRIMARY FAULT | More than one heat pump set as Primary, so units chatter on and off | Multi-heat-pump setup error | Call if it comes back |
MULTI-UNIT COMM FAULT | Secondary heat pump isn't getting a signal from the primary | Primary unit has no power or isn't working | Call if it comes back |
SMART COMM FAULT | No signal from a smart external controller | Automation controller not set up to talk to the heat pump | Call if it comes back |
[BRAND] VS PUMP FAULT | Lost contact with a connected variable-speed pump (Hayward, Jandy, Pentair, Sta-Rite, Aquastar or VGreen), or the pump needs attention | Damaged pump wiring or an internal pump fault | Call if it comes back |
SuperQuiet fault that won’t clear? Our HVAC and EPA 608 certified techs repair AquaCal heat pumps.
FREE to schedule. No obligation. No credit card needed
📄 Official AquaCal manuals: SQ140R manual (PDF) · SQ200R manual (PDF) · Back to model list ↑
AquaCal HeatWave HW160R Error Codes

All fault messages for the AquaCal HeatWave HW160R. It uses the same fault messages as the HeatWave SuperQuiet.
AquaCal HeatWave HW160R Code Table
Code | What It Means | Likely Cause | What to do |
|---|---|---|---|
COMPRESSOR LOCKOUT | Compressor failed to start and went into protection mode | Compressor or start component problem | Turn off & call now |
HIGH PRESSURE FAULT | Refrigerant high pressure switch open | Low water flow (pump off or slow, water diverted away from the heat pump). On cool-only units: fan not running, blocked airflow or a dirty coil | Call soon |
LOW PRESSURE FAULT | Refrigerant low pressure switch open | Fan not running, blocked airflow, dirty evaporator coil or heavy ice on the coil; low refrigerant from a leak | Call soon |
HIGH WATER TEMP | Incoming water above 108°F; heat pump shut off until it drops to 100°F | A gas or solar heater sending hot water straight to the heat pump, or a failed water temperature sensor | Call soon |
HP5 SYSTEM LOCKOUT | Locked out after 5 high pressure faults in one heating or cooling call | The high pressure problem keeps happening. Clears by cycling power | Turn off & call now |
LP5 SYSTEM LOCKOUT | Locked out after 5 low pressure faults in one heating or cooling call | The low pressure problem keeps happening. Clears by cycling power | Turn off & call now |
HPC TEMP SYSTEM LOCKOUT | Control board overheating | Control board or cooling problem | Call soon |
OTA SYSTEM LOCKOUT | Water over a safe temperature (above 110°F) or the two water sensors disagree; heat pump shut off | Out-of-calibration or failed water sensor, or water heated by another source | Call soon |
DEFROST1 / DEFROST2 SENSOR OPEN | Defrost sensor open | Failed defrost sensor or wiring | Call soon |
DEFROST1 / DEFROST2 SENSOR SHORT | Defrost sensor shorted | Failed defrost sensor or wiring | Call soon |
WATER TEMP1 / WATER TEMP2 SENSOR SHORT or OPEN | Water temperature sensor shorted or open; setpoint limited to 96°F until replaced | Failed water sensor or wiring | Call soon |
NO CONTROLLER COMM | Heat pump can't talk to the display board | Loose or damaged cable between the control board and display | Call if it comes back |
ERROR AT PRIMARY UNIT | This is a secondary heat pump and the primary unit has a fault | A fault on the primary heat pump | Call if it comes back |
MULTIPLE PRIMARY FAULT | More than one heat pump set as Primary, so units chatter on and off | Multi-heat-pump setup error | Call if it comes back |
MULTI-UNIT COMM FAULT | Secondary heat pump isn't getting a signal from the primary | Primary unit has no power or isn't working | Call if it comes back |
SMART COMM FAULT | No signal from a smart external controller | Automation controller not set up to talk to the heat pump | Call if it comes back |
[BRAND] VS PUMP FAULT | Lost contact with a connected variable-speed pump (Hayward, Jandy, Pentair, Sta-Rite, Aquastar or VGreen), or the pump needs attention | Damaged pump wiring or an internal pump fault | Call if it comes back |
HeatWave fault that won’t clear? Our HVAC and EPA 608 certified techs repair AquaCal heat pumps.
FREE to schedule. No obligation. No credit card needed
📄 Official AquaCal manuals: HW160R manual (PDF) · Back to model list ↑
AquaCal TropiCal Inverter Error Codes

All error codes for AquaCal TropiCal Inverter heat pumps. They use AL and EA codes. Blue codes are low priority; red codes are urgent.
Models: T70, T100 and T130.
AquaCal TropiCal Inverter Code Table
Code | What It Means | Likely Cause | What to do |
|---|---|---|---|
LOW | Low or no water flow | Pump off, dirty filter, pump too slow, water diverted, or no call for heat from an external controller | Call if it comes back |
AL01 | Discharge temperature sensor failure | Failed sensor or wiring | Call soon |
AL02 | Suction temperature sensor failure | Failed sensor or wiring | Call soon |
AL03 | Inlet water temperature sensor failure | Failed sensor or wiring | Call soon |
AL04 | Outlet water temperature sensor failure | Failed sensor or wiring | Call soon |
AL05 | Coil temperature sensor failure | Failed sensor or wiring | Call soon |
AL06 | Ambient air temperature sensor failure | Failed sensor or wiring | Call soon |
AL07 | Display communication error | Loose or damaged cable between control board and display | Call if it comes back |
AL08 | EEPROM error on the power control board | Control board problem. Cycling power may clear it once | Call soon |
AL09 | Fan error | Fan motor or connection problem | Call soon |
AL10 | High pressure protection | Low water flow, valves in the wrong position, or a refrigerant problem | Call soon |
AL11 | High pressure protection 3 times: locked out | The high pressure problem keeps happening | Turn off & call now |
AL12 | Low pressure protection | Water or air out of operating range, fan not running, blocked airflow, dirty coil, ice, or low refrigerant | Call soon |
AL13 | Low pressure protection 3 times: locked out | The low pressure problem keeps happening | Turn off & call now |
AL14 | Outdoor air too cold or too hot to run (outside 5°–109°F) | Weather, or sun shining directly on the air sensor | Call if it won't clear |
AL15 | Too big a difference between inlet and outlet water temperature | Low water flow: pump off, dirty filter or valves set wrong | Call if it comes back |
AL16 | Inlet/outlet temperature difference 3 times: locked out | The flow problem keeps happening | Call soon |
AL17 | Air too cold for cooling mode | Weather, or a failed air sensor | Call if it won't clear |
AL18 | Compressor protection: discharge temperature too high | Condition that can damage the compressor | Turn off & call now |
AL19 | Voltage protection: too high or too low | Supply voltage problem | Turn off & call now |
AL20 | Current protection: too high or too low | Electrical or compressor problem | Turn off & call now |
AL21 | DC bus voltage protection | Inverter drive problem | Turn off & call now |
AL22 | Compressor over-current protection: locked out | Compressor or drive problem | Turn off & call now |
AL23 | Power module (IPM) temperature too high | Inverter overheating | Call soon |
AL24 | Power module (IPM) error: locked out | Inverter drive problem | Turn off & call now |
AL25 | Compressor driver protection: locked out | Compressor drive problem | Turn off & call now |
EA01 | Over-current protection while speeding up | Inverter drive or compressor problem | Turn off & call now |
EA02 | Over-current protection while slowing down | Inverter drive or compressor problem | Turn off & call now |
EA03 | Over-current protection at constant speed | Inverter drive or compressor problem | Turn off & call now |
EA04 | Over-voltage protection while speeding up | Inverter drive or compressor problem | Turn off & call now |
EA05 | Over-voltage protection while slowing down | Inverter drive or compressor problem | Turn off & call now |
EA06 | Over-voltage protection at constant speed | Inverter drive or compressor problem | Turn off & call now |
EA07 | Communication error between drive and controller | Inverter drive or compressor problem | Call soon |
EA08 | Compressor lost step error | Inverter drive or compressor problem | Turn off & call now |
EA09 | Compressor lost phase error | Inverter drive or compressor problem | Turn off & call now |
EA10 | Power module (IPM) hardware protection | Inverter drive or compressor problem | Turn off & call now |
EA19 | Current test circuit error | Inverter drive or compressor problem | Turn off & call now |
TropiCal Inverter code that won’t clear? Our HVAC and EPA 608 certified techs repair AquaCal inverter heat pumps.
FREE to schedule. No obligation. No credit card needed
📄 Official AquaCal manuals: T70 manual (PDF) · T100 manual (PDF) · T130 manual (PDF) · Back to model list ↑
AquaCal SuperQuiet & TropiCal Error Codes (Previous Models)
Error codes for previous AquaCal SuperQuiet and TropiCal heat pumps. Newer units of these models show text fault messages; older ones show short codes like FLO, HP and FS. Check your display to see which table fits.
Models: SQ120R, SQ125, SQ145, SQ150VS, SQ166R, SQ225, T35, T55, T75, T90, T91, T115, T116, T135, T135R, T170, and TC500 chillers.
Text Fault Messages (Newer Control)
Code | What It Means | Likely Cause | What to do |
|---|---|---|---|
HIGH PRESSURE FAULT | Refrigerant high pressure switch open | Low water flow (pump off or slow, water diverted away from the heat pump). On cool-only units: fan not running, blocked airflow or a dirty coil | Call soon |
LOW PRESSURE FAULT | Refrigerant low pressure switch open | Fan not running, blocked airflow, dirty evaporator coil or heavy ice on the coil; low refrigerant from a leak | Call soon |
HIGH WATER TEMP | Incoming water above 108°F; heat pump shut off until it drops to 100°F | A gas or solar heater sending hot water straight to the heat pump, or a failed water temperature sensor | Call soon |
HP5 SYSTEM LOCKOUT | Locked out after 5 high pressure faults in one heating or cooling call | The high pressure problem keeps happening. Clears by cycling power | Turn off & call now |
LP5 SYSTEM LOCKOUT | Locked out after 5 low pressure faults in one heating or cooling call | The low pressure problem keeps happening. Clears by cycling power | Turn off & call now |
HPC TEMP SYSTEM LOCKOUT | Control board overheating | Control board or cooling problem | Call soon |
VARIABLE DRIVE FAULT | Problem with the variable-speed compressor drive | Drive or compressor problem. Cycling power may clear it once | Call soon |
DEFROST1 / DEFROST2 SENSOR OPEN | Defrost sensor open | Failed defrost sensor or wiring | Call soon |
DEFROST1 / DEFROST2 SENSOR SHORT | Defrost sensor shorted | Failed defrost sensor or wiring | Call soon |
WATER TEMP1 / WATER TEMP2 SENSOR SHORT or OPEN | Water temperature sensor shorted or open; setpoint limited to 96°F until replaced | Failed water sensor or wiring | Call soon |
CLOCK LOW BATTERY | Clock battery low; time resets to default | Clock battery needs replacing | Call if it won't clear |
ERROR AT PRIMARY UNIT | This is a secondary heat pump and the primary unit has a fault | A fault on the primary heat pump | Call if it comes back |
MULTI-UNIT COMM FAULT | Secondary heat pump isn't getting a signal from the primary | Primary unit has no power or isn't working | Call if it comes back |
SMART COMM FAULT | No signal from a smart external controller | Automation controller not set up to talk to the heat pump | Call if it comes back |
NO POOL/SPA GROUP EXISTS | No pool or spa group set up | Only appears when pressing Pool/Spa on a system without presets | Call if it won't clear |
[BRAND] VS PUMP FAULT | Lost contact with a connected variable-speed pump (Hayward, Jandy, Pentair, Sta-Rite, Aquastar or VGreen), or the pump needs attention | Damaged pump wiring or an internal pump fault | Call if it comes back |
Short Codes: FLO, HP, LP, FS, OtA (Older Control)
Code | What It Means | Likely Cause | What to do |
|---|---|---|---|
FLO | Low or no water flow | Pump off, pump too slow, or water diverted away from the heat pump | Call if it comes back |
FS | Defrost cycle: coil is icing up | The heat pump pauses heating for about 10 minutes to melt ice off the coil | Call if it won't clear |
HP | Refrigerant high pressure switch open | Low water flow, or a water pressure switch that needs calibrating | Call soon |
HP5 | Locked out after 5 high pressure faults in one call | The high pressure problem keeps happening. Clears by cycling power | Turn off & call now |
LP | Refrigerant low pressure switch open | Fan not running, blocked airflow, dirty evaporator coil or heavy ice; low refrigerant from a leak | Call soon |
LP5 | Locked out after 5 low pressure faults in one call | The low pressure problem keeps happening. Clears by cycling power | Turn off & call now |
OtA | Incoming water above 110°F; locked until it drops to 100°F | Another heat source sending hot water to the heat pump, or a failed water sensor | Call soon |
pC / pO | Water sensor shorted or open | Failed water sensor or wiring | Call soon |
dPC / dPO | Defrost sensor shorted or open | Failed defrost sensor or wiring | Call soon |
CEr | Communication error between control board and display | Loose or damaged display cable | Call if it comes back |
CSE | Control system error | Controls need a reset (cycle power) | Call if it comes back |
Older AquaCal acting up? We still repair these heat pumps, and if yours is getting old, we’ll tell you honestly whether replacement makes more sense.
FREE to schedule. No obligation. No credit card needed
📄 Official AquaCal manuals: previous models manual (PDF) · 2018 manual (PDF) · Back to model list ↑
How to Reset an AquaCal Heat Pump
- Turn the heat pump off at its control.
- Switch off the breaker or disconnect.
- Wait 5 minutes (at least 2 minutes on TropiCal Inverter models, so the capacitors can discharge).
- Turn the power back on, then the heat pump.
This also clears lockouts like HP5, LP5, AL11 and AL13. If the code comes back, the reset cleared the message but not the cause. Schedule a repair or call 407-786-0000.
When an Error Code Means You Need a Professional
- Quick checks first: FLO, LOW or AL15 (pump, filter and valves), FS (defrost), LP or AL14 in cold weather (clear debris around the coil). If the code comes back, call.
- Call soon: HP or LP that keeps returning, HIGH PRESSURE FAULT, LOW PRESSURE FAULT, sensor codes (pC, pO, dPC, dPO, WATER TEMP, DEFROST, AL01–AL06), OtA, CEr, NO CONTROLLER COMM.
- Stop unit now: HP5, LP5, COMPRESSOR LOCKOUT, and TropiCal Inverter codes AL11, AL13, AL18–AL25 and EA codes. Turn the unit off before calling.


Read our Google Reviews
Why People Choose Us For AquaCal Repairs
- Over 3,000 pool heaters repaired across Florida
- EPA 608 & HVAC certified technicians
- Replacement parts for all brands and models
- Licensed and insured
- Serving customers across Florida and nationwide
Need help? Call us at 407-786-0000 or visit our pool heater repair page to learn more
FAQs
What does FLO mean on an AquaCal heat pump?
FLO means little or no water is flowing through the heat pump. Make sure the pump is on (run a variable-speed pump faster), the filter is clean and not in backwash, and water isn’t being diverted away from the heat pump. If it comes back with good flow, the water pressure switch may need adjusting or replacing. Schedule a repair or call 407-786-0000.
What does HP mean on an AquaCal heat pump?
HP (or HIGH PRESSURE FAULT on current models) means the refrigerant high pressure switch opened, usually from low water flow. HP5 means it happened 5 times in one heating call and the heat pump locked out; cycle power to clear it. If it keeps happening with good flow, have it checked. Schedule a repair or call 407-786-0000.
What does LP mean on an AquaCal heat pump?
LP (or LOW PRESSURE FAULT) means the refrigerant low pressure switch opened. Check that the fan runs and nothing blocks airflow around the coil. On a warm day, LP is often a refrigerant leak, which only an EPA 608 certified tech can repair. Schedule a repair or call 407-786-0000.
What does FS mean on an AquaCal heat pump?
FS means the heat pump is in a defrost cycle. It pauses heating for about 10 minutes to melt ice off the coil, and you may see steam. If FS keeps coming back or shows on mild days, the defrost sensor may be failing. Schedule a repair or call 407-786-0000.
What does OtA mean on an AquaCal heat pump?
OtA means the water coming in is above about 110°F, so the heat pump locked out until it drops to 100°F. Check whether a gas or solar heater is sending hot water straight into it. If not, a water sensor is likely reading wrong. Schedule a repair or call 407-786-0000.
How do I reset my AquaCal heat pump?
Turn the heat pump off, switch off the breaker or disconnect, wait 5 minutes (at least 2 on TropiCal Inverter models), then turn it back on. That also clears lockouts like HP5 and LP5. If the code comes back, the cause is still there.
What do AL and EA codes mean on an AquaCal TropiCal?
The TropiCal Inverter (T70, T100, T130) uses AL and EA codes. AL01–AL06 are sensors, AL10–AL13 are refrigerant pressure, AL14–AL17 are temperature limits, and AL18–AL25 and the EA codes are compressor and inverter protections that need a certified tech. Schedule a repair or call 407-786-0000.
Can I fix an AquaCal error code myself?
A few clear once you fix the cause, like turning the pool pump back on (FLO, LOW) or waiting out a defrost cycle (FS). Most others, including refrigerant, sensor, and inverter codes, need a certified tech. Call 407-786-0000 and we’ll tell you over the phone whether it needs a visit.
Is it time for a new pool heater?
If your AquaCal heat pump is beyond repair, we can help. See our pool heater replacement options to find the right heat pump for your pool.
Still dealing with a broken pool heater?
You don’t have to. Certified technicians, fast reliable service, guaranteed repairs. Call or click to get started.